Application:
The meter is used for precise doing system which need to adjust the PH/ORP value accurately, the application fields including: Industry process, waste water treatment, Water Reuse Systems, Circuit Board waste water , electroplating waste water treatment, medical industry and etc. It can meet the requirements of backlash and dead area control in chemical, medicine reaction and neutralization process. And it is also meet the requirements of intelligent configuration transmitting control systems in PID close loop adjustment, difference value control, switch control, pulse frequency / duty cycle control, current transmitting, doing tank level management.
Features:
Electronic chemical inline measurement +sensor +PLC+professional software=system integration
Multi channels ( pH or ORP , pH+ORP,TEMP) sensors for inline measurement
Dynamic PID adjustment, PWM pulse, controlling metering pump to achieve the precise measurement
Professional solutions for electroplating process waste water treatment. Double channels ORP different value dynamic control.
Driving solutions for various dosing pumps, Static switch, and PWM
Dosing low level alarm avoids dosing error.
Multi-function sampling flow device needs only a little sample
Flow chart of system control
Model: POP-6902
Case material: ABS
Installation: wall mounted or bottom installation
Protection level: IP65 (water proof nut wire in≥5mm)
pH measurement: pH measurement:pH sensor
pH range :2.0 ~ 12.0
Resolution:pH: 0.02
Accuracy:pH: ±0.2
Stabitity: ±0.06/24h
temperature:0 ~ 40℃
ORP measurement: ORP measurement:ORP sensor
ORP range:-1999mV ~ +1999mV
Accuracy:±5mV
Resolution:1mV
Stability:±5mV/24h
Temperature:0 ~ 40℃
Water temperature measurement: Component:Pt1000
Accuracy:±0.5℃
Range:0~99.9℃
Resolution:0.1
℃
Stablility: ±5℃/24h
Switch signal input:
Pull-up voltage 12VDC, photoelectricity seclusion
Dosing tank, Low water level switch
(or other normal open digital switch): double channels
Switch signal output:
Relay output:3 channels
Dry Contact output,Load capability:3A/AC 240V(max)
3A/DC 30V(max)
OC output:2 channels
External power supply,load current 25mA( at DC 5V)load voltage DC24V(Max)
Analog Communication:
4-20mA output
Double channels, isolated, configuration, transferable,
reversible, inside/outside power supply selectable .max.
loop impedance 300oHm, accuracy< ±1%
Communication port: RS-485 serial interface ,one channel
Interface:
240x160 LCD display,backlight white/green can be set,
six digits graphics button
Working environment: temperature:0~60℃ humidity ≤90%RH
Power supply: AC/DC 18V~36V;Power consumption:≤5W